130
Figure 6.101: Examples of Contact voltage measurement result
6.2.28 RCD t
– Trip-out time
Warning!
MI 3325 checks voltage on RCD-PE before running test and disables test in case
the hazardous live voltage is detected. In this case, immediately remove supply
from tested circuit, find, and eliminate problem before any other activity! See
chapter
1.2 Testing potential on TP1-PE terminal for installation tests
information.
Figure 6.102: Trip-out time RCD t test menu
Test results / sub-results
t ∆N
Trip-out time
t I∆N (+)
Trip-out time ((+) positive polarity)
t I∆N (-)
Trip-out time ((-) negative polarity)
Uc
Contact voltage
Test parameters
Use
RCD / PRCD selection [fixed, PRCD, PRCD-S, PRCD-K]
Selectivity
Characteristic [G, S]
Type
RCD type [AC, A, F, B, B+]
I
∆
N
Rated RCD residual current sensitivity [10 mA, 15 mA, 30 mA, 100 mA, 300
mA, 500 mA, 1000 mA]
X I
∆
N
Multiplication factor for test current [0.5, 1, 2, 5]
Phase
Starting polarity [(+), (-), (+,-)]
Test
Test [-, L/PE, L1/PE, L2/PE, L3/PE]
RCD standard
RCD standard [EN 61008 / EN 61009, IEC 60364-4-41 TN/IT, IEC 60364-4-