Section 7
Refrigeration System
7-16
Safety Limit #3
Compressor discharge temperature fell below 85
°
F/29.4
°
C for 3 consecutive harvest cycles.
Possible Cause
Check/Correct
Improper installation
•
See “Installation/Visual Inspection Checklist” on page 7-10
Ice thickness probe
•
Check thickness setting
Water system - insufficient
water flow over evaporator
•
Low water pressure (20 psi min.)
•
Loss of water from sump area
•
Clogged water distribution tube
•
Dirty/defective float valve
•
Dirty/defective water dump valve
•
Defective water pump
Refrigeration system
•
Non-Manitowoc components
•
Defective head pressure control valve (remotes)
•
Defective harvest pressure control (HPR) valve (remotes)
•
Defective fan cycle control
•
Improper refrigerant charge
•
Defective hot gas valve
•
TXV flooding (check bulb mounting)
Thermistor
•
Defective thermistor
Safety Limit #4
Compressor discharge temperature exceeded 255
°
F/123.8
°
C for 15 continuous seconds.
Possible Cause
Check/Correct
Improper installation
•
See “Installation/Visual Inspection Checklist” on page 7-10
Restricted condenser
air flow (air-cooled models)
•
High inlet air temperature (110
°
F/43.3
°
C max.)
•
Condenser air recirculation discharge
•
Dirty condenser filter
•
Dirty condenser fins
•
Defective fan cycling control
•
Defective fan motor
Restricted condenser water
flow (water-cooled models)
•
Low water pressure (20 psi min.)
•
High water temperature (90
°
F/32.2
°
C max.)
•
Dirty condenser
•
Dirty/defective water regulating valve
•
Water regulating valve out of adjustment
Refrigeration system
•
Non-Manitowoc components
•
Defective head pressure control valve (remotes)
•
Improper refrigerant charge
•
Non-condensibles in refrigeration system
•
High side refrigerant lines/component restricted or plugged
•
TXV starving (check bulb mounting)
•
Defective compressor
Thermistor
•
Defective thermistor
NOTE: Because there are many possible external
problems, do not limit your diagnosis to only the
items listed in these charts.
NOTE: Safety Limits #3 and #4 are not used on later
production J-model ice machines. Any fault that
would stop the ice machine on safety limit #3 or #4
would also stop the ice machine on safety limit #1 or
#2.
Содержание J-1300
Страница 1: ...J Model Service Manual 1997 Manitowoc Ice Inc Part No 83 5631 9 Rev A 8 97 Ice Machines ...
Страница 10: ...Warranty Section 1 1 2 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...Section 2 Installation References 2 4 deflector is compatible with Manitowoc ice machines ...
Страница 29: ...Section 2 Installation References 2 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...Section 3 Maintenance 3 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...Section 6 Electrical System 6 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...Section 7 Refrigeration System 7 43 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 164: ......