Section 6
Electrical System
6-53
Diagnosing Ice Machine That Will Not Run
WARNING
High (line) voltage is applied to the control board
(terminals #55 and #56) at all times. Removing
control board fuses or moving the toggle switch to
OFF will not remove the power supplied to the
control board.
Step
Check
Notes
1
Verify primary voltage supply to ice
machine.
Verify that the fuse or circuit breaker is closed.
2
Verify the high pressure cut-out is closed.
The H.P.C.O. is closed if primary power voltage is present at
terminals #55 and #56 on the control board.
3
Verify main and transformer (if
applicable) control board fuses are OK.
If the bin switch light functions, the fuses are OK.
4
Verify the bin switch functions properly.
A defective bin switch can falsely indicate a full bin of ice.
5
Verify ICE/OFF/CLEAN toggle switch
functions properly.
A defective toggle switch may keep the ice machine in the
OFF mode.
6
Verify low DC voltage is properly
grounded.
Loose DC wire connections may intermittently stop the ice
machine.
7
Replace the control board.
Be sure Steps 1-6 were followed thoroughly. Intermittent
problems are not usually related to the control board.
Содержание J-1300
Страница 1: ...J Model Service Manual 1997 Manitowoc Ice Inc Part No 83 5631 9 Rev A 8 97 Ice Machines ...
Страница 10: ...Warranty Section 1 1 2 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...Section 2 Installation References 2 4 deflector is compatible with Manitowoc ice machines ...
Страница 29: ...Section 2 Installation References 2 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...Section 3 Maintenance 3 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...Section 6 Electrical System 6 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...Section 7 Refrigeration System 7 43 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 164: ......