Section 2
Installation References
2-14
CALCULATING REMOTE CONDENSER
INSTALLATION DISTANCES
Line Set Length
The maximum length is 100’ (30.5 m).
The ice machine compressor must have the proper oil
return. The receiver is designed to hold a charge
sufficient to operate the ice machine in ambient
temperatures between -20
°
F (-28.9
°
C) and 130
°
F
(54.4
°
C), with line set lengths of up to 100’ (30.5 m).
Line Set Rise/Drop
The maximum rise is 35’ (10.7 m).
The maximum drop is 15’ (4.5 m).
CAUTION
If a line set has a rise followed by a drop, another
rise cannot be made. Likewise, if a line set has a
drop followed by a rise, another drop cannot be
made.
Calculated Line Set Distance
The maximum distance is 150’ (45.7 m).
Line set rises, drops, horizontal runs (or combinations
of these) in excess of the stated maximums will
exceed compressor start-up and design limits. This
will cause poor oil return to the compressor.
Make the following calculations to make sure the line
set layout is within specifications.
1.
Insert the
measured rise
into the formula below.
Multiply by 1.7 to get the
calculated rise
.
(Example: A condenser located 10 feet above the
ice machine has a
calculated rise
of 17 feet.)
2.
Insert the
measured drop
into the formula below.
Multiply by 6.6 to get the
calculated drop
.
(Example. A condenser located 10 feet below the
ice machine has a
calculated drop
of 66 feet.)
3.
Insert the
measured horizontal distance
into the
formula below. No calculation is necessary.
4.
Add together the
calculated rise
,
calculated
drop
, and
horizontal distance
to get the
total
calculated distance
. If this total exceeds 150’
(45.7 m), move the condenser to a new location
and perform the calculations again.
Maximum Line Set Distance Formula
Step 1.
Measured Rise (35’ [10.7 m] Maximum)
______ x 1.7 =
_______ Calculated Rise
Step 2.
Measured Drop (15’ [4.5 m] Maximum)
______ x 6.6 =
_______ Calculated Drop
Step 3.
Measured Horizontal Distance (100’ [30.5 m] Maximum) =
_______ Horizontal Distance
Step 4.
Total Calculated Distance 150’ (45.7 m) =
_______ Total Calculated Distance
Combination of a Rise
and a Horizontal Run
Combination of a Drop
and a Horizontal Run
Combination of a Rise, a Drop
and a Horizontal Run
SV1194
SV1195
SV1196
H
H
H
R
D
R
D
Содержание J-1300
Страница 1: ...J Model Service Manual 1997 Manitowoc Ice Inc Part No 83 5631 9 Rev A 8 97 Ice Machines ...
Страница 10: ...Warranty Section 1 1 2 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...Section 2 Installation References 2 4 deflector is compatible with Manitowoc ice machines ...
Страница 29: ...Section 2 Installation References 2 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...Section 3 Maintenance 3 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...Section 6 Electrical System 6 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...Section 7 Refrigeration System 7 43 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 164: ......