Section 2
Installation References
2-10
Water Connections and Drains
CAUTION
Plumbing must conform to local and state
codes.
Location
Water
Temperature
Water
Pressure
Female Pipe Fitting
(F.P.T.)
1
Size
Tube Size Up to Ice
Machine Fitting
Ice making
water inlet
33
°
F (0.6
°
C) min.
90
°
F (32.2
°
C) max
20 psi min.
80 psi max
3/8” F.P.T.
3/8”
Ice making
water drain
-
-
1/2” F.P.T.
1/2”
Condenser
water inlet
33
°
F (0.6
°
C) min.
90
°
F (32.2
°
C) max
20 psi min.
150 psi max
J1300/J1800 - 1/2” F.P.T.
All Others - 3/8” F.P.T.
Condenser
Water Drain
-
-
1/2” F.P.T.
1/2”
Bin Drain
-
-
3/4” F.P.T.
3/4”
1
F.P.T. - Female Pipe Thread
CONDENSER WATER
DRAIN FITTING
1/2” F.P.T.
SV1304
CONDENSER WATER
INLET FITTING
1/2” F.P.T.
CONDENSER WATER
DRAIN TUBING
1/2” MIN. I.D.
CONDENSER WATER
INLET TUBING
1/2” MIN. I.D.
WATER
SHUT OFF
VALVE
ICE MAKING WATER
DRAIN FITTING
1/2” F.P.T.
ICE MAKING WATER
DRAIN TUBING
1/2” MIN. I.D.
OPEN, TRAPPED OR
VENTED DRAIN
VENT
SLOPE
BIN DRAIN
TUBING
3/4” MIN. I.D.
BIN DRAIN
FITTING
3/4” F.P.T.
18”
VENT
ICE MAKING WATER
INLET FITTING
3/8” F.P.T.
ICE MAKING WATER
INLET TUBING
3/8” MIN. I.D.
Содержание J-1300
Страница 1: ...J Model Service Manual 1997 Manitowoc Ice Inc Part No 83 5631 9 Rev A 8 97 Ice Machines ...
Страница 10: ...Warranty Section 1 1 2 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...Section 2 Installation References 2 4 deflector is compatible with Manitowoc ice machines ...
Страница 29: ...Section 2 Installation References 2 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...Section 3 Maintenance 3 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...Section 6 Electrical System 6 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...Section 7 Refrigeration System 7 43 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 164: ......