Section 7
Refrigeration System
7-3
REMOTE MODELS
Remote Pre-Chill and Freeze Cycle (Models J450/J600/J800/J1000)
Prechill Refrigeration Sequence
No water flows over the evaporator during the
prechill. The refrigerant absorbs heat (picked up
during the harvest cycle) from the evaporators. The
suction pressure decreases during the prechill.
Freeze Cycle Refrigeration Sequence
The refrigerant absorbs heat from the water running
over the evaporator surface. The suction pressure
gradually drops as ice forms.
The headmaster control valve maintains discharge
pressure in cold ambient temperatures. (See
“Headmaster Control Valve” on page 7-28.)
SV1566
EVAPORATOR
HEAT
EXCHANGER
EXPANSION
VALVE
HOT GAS
SOLENOID VALVE
STRAINER
REMOTE
CONDENSER
RECEIVER
SERVICE VALVE
COMPRESSOR
DRIER
HIGH PRESSURE VAPOR
HIGH PRESSURE LIQUID
LOW PRESSURE VAPOR
LOW PRESSURE LIQUID
LIQUID LINE
SOLENOID
VALVE
RECEIVER
CHECK VALVE
CHECK VALVE
HARVEST
PRESSURE
REGULATING
VALVE
HARVEST
PRESSURE
REGULATING
SOLENOID VALVE
HEAD
PRESSURE
CONTROL
VALVE
C
B
R
Содержание J-1300
Страница 1: ...J Model Service Manual 1997 Manitowoc Ice Inc Part No 83 5631 9 Rev A 8 97 Ice Machines ...
Страница 10: ...Warranty Section 1 1 2 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 14: ...Section 2 Installation References 2 4 deflector is compatible with Manitowoc ice machines ...
Страница 29: ...Section 2 Installation References 2 18 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 45: ...Section 3 Maintenance 3 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 105: ...Section 6 Electrical System 6 54 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 148: ...Section 7 Refrigeration System 7 43 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 164: ......