Open-loop Motor A5
60
Detailed description
MOTOR ID
(Motor Identification)
This parameter allows for the selection of
specific sets of motor parameters. A listing of
each Motor Ids with its corresponding set of
motor parameters is shown below.
Motor
ID
motor
parameter
4 pole
400 v
4 pole
200 v
6 pole
400 v
6 pole
200 v
Rated Mtr
Power
0.0
HP/KW
0.0
HP/KW
0.0
HP/KW
0.0
HP/KW
Rated Mtr
Volts
0.0 V
0.0 V
0.0 V
0.0 V
Rated Excit
Freq
0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
Motor Mid
Volts
28.0V
14.0V
28.0V
14.0V
Motor Mid
Freq
3.0Hz
3.0Hz
3.0Hz
3.0Hz
Motor Min
Volts
9.0V
4.0V
9.0V
4.0V
Motor Min
Freq
1.0Hz
1.0Hz
1.0Hz
1.0Hz
Rated Motor
Curr
0.0 A
0.0 A
0.0 A
0.0 A
Motor
Poles
4 4 6 6
Rated Mtr
Speed
0.0
rpm
0.0
rpm
0.0
rpm
0.0
rpm
% No Load
Curr
35.0% 35.0% 45.0% 45.0%
Stator
Leakage X
9.0% 9.0% 7.5% 7.5%
Rotor
Leakage X
9.0% 9.0% 7.5% 7.5%
Stator
Resist
2.5% 2.5% 2.5% 2.5%
Motor Iron
Loss
0.5% 0.5% 0.5% 0.5%
Motor Mech
Loss
1.0% 1.0% 1.0% 1.0%
Motor ID Parameters
NOTE: The default motor selections need to
have the motor nameplate information entered in
the appropriate motor parameters. The other
motor parameters are already set to nominal
values.
RATED MTR PWR
(
Rated Motor Power)
This parameter sets the rated power in
horsepower (HP) or kilowatts (kW) of the motor.
Note: value should be obtained from the motor
nameplate
RATED MTR VOLTS
(
Rated Motor Voltage)
This parameter sets the rated motor voltage.
Note: value should be obtained from the motor
nameplate
RATED EXCIT FREQ
(
Rated Motor Excitation Frequency)
This parameter sets the excitation frequency of
the motor. Note: value should be obtained from
the motor nameplate
MOTOR MID VOLTS
(
V/Hz Pattern Voltage at Middle Frequency)
This parameter sets rated voltage at the V/Hz
pattern middle frequency. This setting is limited
by the motor’s rated voltage (RATED MTR
VOLTS(A5)). Note: a SETUP FLT #9 will occur
if the below formula is not meet.
<
<
VOLTS
MTR
RATED
VOLTS
MID
MOTOR
VOLTS
MIN
MOTOR
MOTOR MID FREQ
(
V/Hz Pattern Middle Frequency)
This parameter sets middle frequency used to
define the V/Hz pattern. Note: a SETUP FLT #9
will occur if the below formula is not meet.
<
<
FREQ
EXCIT
RATED
FREQ
MID
MOTOR
FREQ
MIN
MOTOR
MOTOR MIN VOLTS
(
V/Hz Pattern Voltage at Minimum Frequency)
This parameter sets voltage at the V/Hz pattern
minimum frequency. Note: a SETUP FLT #9 will
occur if the below formula is not meet.
<
<
VOLTS
MTR
RATED
VOLTS
MID
MOTOR
VOLTS
MIN
MOTOR