Specifications
6
Drive Derating
Altitude Derating
Control ratings apply to 1000 meters (3300 feet)
altitude without derating. For installations at
higher altitudes, derate both the continuous and
peak current levels 5% for each 300 m (1000 ft)
above 1000 m (3300 ft).
Derating for Carrier Frequency
Control ratings apply for carrier frequencies up
to and including 10 kHz. Above that linearly
derate both the continuous and peak current
levels by 5% for each 1kHz.
Derating for Single Phase Input Power
For single phase input power, derate both the
continuous and peak current levels by 50%.
Drive Model Number
The HPV 600 nameplate contains the model
number, which provides complete identification
of the drive.
HPV 600 Model Numbers
HPV 600
-
-
-
drive
input voltage
2 = 230 volt
4 = 460/400 volt
continuous
output current
option #1
0 = no encoder option card
(open-loop)
R = incremental encoder card
(closed-loop)
option #2
0 = no option card
2 = RS-422 and analog outputs card
4 = RS-422 card
8 = RS-485 card
operator
E = elevator operator
N = no operator
software program
control board
1,2 = Fixed terminal blocks
(North America)
3 = Fixed terminal blocks
(European)