Closed-loop Motor A5
100
Detailed description
MOTOR ID
(Motor Identification)
This parameter allows for the selection of
specific sets of motor parameters. A listing of
each Motor Ids with its corresponding set of
motor parameters is shown below.
motor parameter
Motor ID
4 pole dflt
6 pole dflt
Rated Mtr Power 0.0 HP/KW 0.0 HP/KW
Rated Mtr Volts
0.0 V
0.0 V
Rated Excit Freq 0.0 Hz
0.0 Hz
Rated Motor Curr 0.0 A
0.0 A
Motor Poles
0
0
Rated Mtr Speed 0.0 rpm
0.0 rpm
% No Load Curr
35.00%
45.00%
Stator Leakage X 9.00%
7.50%
Rotor Leakage X 9.00%
7.50%
Stator Resist
1.50%
1.50%
Motor Iron Loss
0.50%
0.50%
Motor Mech Loss 1.00%
1.00%
Flux Sat Break
75%
75%
Flux Sat Slope 1
0%
0%
Flux Sat Slope 2
50%
50%
Motor ID Parameters
NOTE: The default motor selections need to
have the motor nameplate information entered in
the appropriate motor parameters. The other
motor parameters are already set to nominal
values.
RATED MTR PWR
(
Rated Motor Power)
This parameter sets the rated power in
horsepower (HP) or kilowatts (kW) of the motor.
Note: value should be obtained from the motor
nameplate
RATED MTR VOLTS
(
Rated Motor Voltage)
This parameter sets the rated motor voltage.
Note: value should be obtained from the motor
nameplate
RATED EXCIT FREQ
(
Rated Motor Excitation Frequency)
This parameter sets the excitation frequency of
the motor. Note: value should be obtained from
the motor nameplate
RATED MOTOR CURR
(
Rated Motor Amps)
This parameter sets the rated motor current.
Note: value should be obtained from the motor
nameplate
MOTOR POLES
(Motor Poles)
This parameter sets the number of poles in the
motor.
NOTE: This must be an even number or a
Setup Fault #3 will occur. Note: value should be
obtained from the motor nameplate or use table
below as reference
Rated
#
of
Speed
motor
(RPM)
poles
1300-1802 4
900-1202 6
660-900 8
RATED MTR SPEED
(
Rated Motor Speed)
This parameter sets the rated rpm of the motor
(nameplate speed). NOTE: This is a function of
the motor only and does not need to be the
same as the CONTRACT MTR SPD (A1)
parameter setting. Note: value should be
obtained from the motor nameplate or use table
below as reference
Rated
#
of
Speed
motor
(RPM)
poles
1300-1803 4
900-1203 6
660-900 8
% NO LOAD CURR
(Percent No Load Current)
This parameter sets the percent no load current
of the motor.
STATOR LEAKAGE X
(Stator Leakage Reactance)
This parameter sets the stator reactance
leakage, as a percent of the BASE IMPEDANCE
(D2), which appears in the Power Data display.
NOTE: The base impedance is based on the
RATED MTR PWR (A5) and RATED MTR
VOLTS (A5) parameters.