Open-loop Start-up
11
Performance Adjustments
Stalling Attempting to Lift Load
If the motor stalls as it attempts to lift the load,
then until resolved, try the following (in order):
1. Increase the Torque Boost Gain
parameter
2. Adjust the Motor Stator Resistance
parameter
3. Adjust the Motor Mid Voltage parameter
Note: if no performance change is observed
after any one step, set any changed value(s)
back to the original value(s) before
proceeding onto the next step.
Increase the Torque Boost Gain Parameter
•
The Torque Boost function is defaulted
off (TORQ BOOST GAIN (A1)= 0).
•
Increase the TORQ BOOST GAIN (A1)
in 0.1 intervals and observe
performance.
Adjust the Motor’s Stator Resistance
•
Measure the stator resistance by
completing the procedure detailed on
page 16.
•
If still stalling after measuring stator
resistance, additionally increase
STATOR RESIST (A5) parameter
(increase increments of 0.1 and observe
performance)
Adjust the Motor Mid Voltage Parameter
•
Complete the Mid-volts Adjustment
Procedure detailed on page 16.
•
If still stalling after completing mid-volts
adjustment procedure, additionally
increase MOTOR MID VOLTS (A5)
parameter (increase increments of 0.5
and observe performance)
•
Note: Avoid increasing the MOTOR MID
VOLTS (A5) parameter too high, since
this effects stopping performance (i.e.
coming into the floor too fast) or can
create Overcurrent Faults
Undershooting
Floor
(page 14)
Overshooting
Floor
(page 15)
...only with
Regen Load
(page 15)
Coming into
Floor Too
Fast
(page 13)
Stalling
Attempting to
Lift Load
(page 11)
Rollback or
Bump at Start
(page 12)
Decreasing
Take-off Time
(page 12)
Spotting or
Stalling Going
into Leveling
(page 13)
Rollback at
Stop
(page 15)
Bump
at Stop
(page 14)
Leveling
Speeds/Times
Different Up vs Down
(page 14)
Leveling
Oscillation
(page 14)
Overcurrent
Faults
(page 12)