Closed-loop Logic Inputs C2
116
run up
(Run Up)
If drive is enabled through the DRIVE ENABLE
logic input, this function will start drive operation
with positive speed commands.
Note: if both RUN UP and RUN DOWN are true
then the run is not recognized.
Note: if DIR CONFIRM (C1) is enabled, this
input is also used to confirm the polarity of the
analog speed command as well as starting the
operation of the drive.
s-curve sel 0
(S-Curve Select bit-0)
s-curve sel 1
(S-Curve Select bit-1)
These two bits are used to select one of four s-
curve selections.
ser2 insp ena (Serial Mode 2 Inspection Enable)
Used only with custom serial protocol (mode 2)
Defines the logic input to be used as one of the
two sources of inspection run command when
using serial mode 2. This input must be true as
well as a comparable inspection run command
sent serially for the drive to run in inspection
mode.
step ref b0
(Speed Selection bit-0)
step ref b1
(Speed Selection bit-1)
step ref b2
(Speed Selection bit-2)
step ref b3
(Speed Selection bit-3)
Four inputs, which must be used together as a
4-bit command for multi-step speed selection.
trq ramp down
(Torque Ramp Down Signal)
This function works only if the RAMP STOP SEL
(C1) switch is set to RAMP TO STOP and
RAMP DOWN EN SRC (C1) is set to
EXTERNAL TB1.
up/dwn
(Up/Down Signal)
This signal is used to change the sign of the
speed command. Default is FALSE; therefore,
positive commands are for the up direction and
negative speed command are for the down
direction. Making this input true reverses the
car’s direction.