Lite-On Technology Corp.
Industrial Automation
139
PD-04
COT
The setting for the communication timeout
Communication
address:
0308H
0309H
Initial value
0
Control mode
ALL
Unit
Sec
Configuration range
0 ~ 20
Data size
16bit
Data format
Dec
If the setting value is not 0, turn on the communication timeout immediately; otherwise, turn it off.
PD-06
(N-keep)
SWDI
Control switch for the source of the input
contact (DI)
Communication
address:
030CH
030DH
Initial value
0
Control mode
ALL
Unit
N/A
Configuration range
0 ~ 1
Data size
16bit
Data format
Dec
0: The DI status is controlled by the external contact.
1: The DI status is controlled by the software. (The DI status can be set via PD-32.)
PD-07
CDT
The time for the delay of the communication
response
Communication
address:
030EH
030FH
Initial value
0
Control mode
ALL
Unit
1ms
Configuration range
0 ~ 1000
Data size
16bit
Data format
Dec
This delays the communication time needed for the drive to respond to the upper controller.