Configuration
2−103
l
EDSVF9383V−EXT EN 2.0
2.4.33.2
Conversion
The analog input signal at FEVAN1−IN is converted into the corresponding value of the target using
C1093 (numerator) and C1094 (denominator). At the same time, it is adapted to the suitable data
format.
Tip!
Make sure that the input signal is processed unscaled (100% correspond to 16384) when
determining the values for C1093 and C1094.
For the decimal positions of the target code, always multiply the value to be transmitted with the
factor 10000.
Mandatory:
Valueofthetargetcode
+
ƪ
Inputsignal[%]
@
16384
100
@
C1093
C1094
)
C1095
ƫ
@
1
10000
Example 1
A signal of 100 % is to result in a maximum current I
max
(C0022) of 10 A.
l
The input signal of 100 % results in an input value of 16384.
l
The value to be transmitted (C1090) must be 100000 (10 A
×
10000).
l
Enter these values in C1093 (numerator) and C1094 (denominator):
C1093
C1094
+
Valuetobetransmitted
Inputvalue
+
100000
16384
Example 2
A signal of 10 % ... 50 % is to result in an acceleration time T
ir
(C0012) of 1.5 s ... 7.5 s.
l
The input signal of 50 % results in an input value of 8192.
l
The value to be transmitted (C1090) must be 75000 (7.5 s
×
10000).
l
Enter these values in C1093 (numerator) and C1094 (denominator):
C1093
C1094
+
Valuetobetransmitted
Inputvalue
+
75000
8192
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...