2.4.54
Sample & Hold (S&H)
This FB can accept analog signals and save them non−volatile. The saved value is also available after
mains disconnection.
C0572
S&H1
S&H1−OUT
S&H1−IN
C0573
S&H1−LOAD
C0570
C0571
S&H
Fig. 2−132
Sample & Hold (S&H1)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
S&H1−IN
a
C0572
dec [%]
C0570
1
1000
S&H1−LOAD
d
C0573
bin
C0571
2
1000
LOW = save
S&H1−OUT
a
−
−
−
−
−
Function
l
With S&H1−LOAD = HIGH the signal at the input S&H1−IN is switched to the output
S&H1−OUT.
l
With S&H1−LOAD = LOW the output S&H1−OUT is disconnected from the input S&H1−IN and
outputs the value which was last valid and S&H−OUT outputs the value which was accepted
last.
l
Saving before mains disconnection:
– The value which was accepted last is saved non−volatile in the internal memory before the
supply voltage is switched off. When the supply voltage is switched on, the saved value is
loaded into the FB S&H1.
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...