Configuration
2−146
l
EDSVF9383V−EXT EN 2.0
+
-
C 1 3 3 4
C 1 3 3 5
P C T R L 2 - S E T
C 1 3 3 0
C 1 3 3 1
P C T R L 2 - O U T
C 1 3 4 0 / 2
P C T R L 2
± 1 0 0 %
R E S E T
C 1 3 4 1 / 1
P C T R L 2 - R F G - L O A D
C 1 3 4 5 / 1
C 1 3 4 0 / 1
P C T R L 2 - R F G - S E T
C 1 3 4 4 / 1
C 1 3 4 4 / 2
C 1 3 3 2
C 1 3 3 3
C 1 3 3 6
C 1 3 3 7
P C T R L 2 - A C T
C 1 3 4 0 / 3
C 1 3 4 4 / 3
C 1 3 4 1 / 2
P C T R L 2 - I - O F F
C 1 3 4 5 / 2
C 1 3 4 1 / 3
P C T R L 2 - I N A C T
C 1 3 4 5 / 3
P C T R L 2 - I N F L
C 1 3 4 0 / 4
C 1 3 4 4 / 4
C 1 3 4 1 / 4
P C T R L 2 - O V E R L A Y
C 1 3 4 5 / 4
R F G = 0
Fig. 2−122
Process controller (PCTRL2)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
PCTRL2−RFG−SET
a
C1344/1
dec [%]
C1340/1
1
1000
The process setpoint is shown at
PCTRL2−SET with any start value via a
ramp generator.
The function is activated using
PCTRL−RFG−LOAD.
PCTRL2−RFG−LOAD
d
C1345/1
bin
C1341/1
2
1000
HIGH = Function of PCTRL2−RFG−SET is
active
PCTRL2−SET
a
C1344/2
dec [%]
C1340/2
1
1000
Input for process setpoint. Possible value
range: ±200 %. The time of step−change
signals can be decelerated via the ramp
generator (C1330 for the acceleration time;
C1331 for the deceleration time).
PCTRL2−ACT
a
C1344/3
dec [%]
C1340/3
1
1000
Input for actual value; value range ±200 %
PCTRL2−INFL
a
C1344/4
dec [%]
C1340/4
1
1000
Evaluation (influence) of the output signal;
value range ±200 %
PCTRL2−I−OFF
d
C1345/2
bin
C1341/2
2
1000
HIGH = switch off I component (online)
LOW = switch off I component (online)
PCTRL2−INACT
d
C1345/3
bin
C1341/3
2
1000
HIGH = Inactivation of the process
controller (online)
PCTRL2−OVERLAY
d
C1345/4
bin
C1341/4
2
1000
HIGH = Show influence
LOW = Hide influence
PCTRL2−OUT
a
−
−
−
−
−
−
Range of functions
l
Control characteristic
l
Ramp generator
l
Value range of the output signal
l
Evaluating the output signal
l
Deactivating the process controller
Содержание 9300 vector Series
Страница 8: ...Preface Definition of notes used 1 6 l EDSVF9383V EXT EN 2 0...
Страница 188: ...Application examples Centre winder with internal diameter calculation 3 18 l EDSVF9383V EXT EN 2 0...
Страница 192: ...Signal flow charts Speed control 4 4 l EDSVF9383V EXT EN 2 0 Fig 4 1 Basic configuration 1000 speed control sheet 1...
Страница 205: ...Signal flow charts Step control 4 17 l EDSVF9383V EXT EN 2 0 Fig 4 13 Basic configuration 2000 step control sheet 1...
Страница 211: ...Signal flow charts Torque control 4 23 l EDSVF9383V EXT EN 2 0 Fig 4 17 Basic configuration 4000 torque control sheet 1...