Configuration
2−60
l
EDSVF9383V−EXT EN 2.0
Function
Code
Value
Function
C0338 for ARIT1
C0600 for ARIT2
C0603 for ARIT3
0
·
ARITx−OUT = ARITx−IN1
– ARITx−IN2 is not processed
1
·
ARITx−OUT = ARITx−IN1 + ARITx−IN2
– Example: 100 % = 50 % + 50 %
2
·
ARITx−OUT = ARITx−IN1 − ARITx−IN2
– Example: 50 % = 100 % − 50 %
3
·
ARITx−OUT = ARITx−IN1 * ARITx−IN2
– Example: 100 % = 100 % * 100 %
4
·
ARITx−OUT = ARITx−IN1 / |ARITx−IN2|
– Example: 1 % = 100% / 100%
5
·
ARITx−OUT = ARITx−IN1 / (100 % − ARITx−IN2)
– Example: 200 % = 100 % / (100 % − 50 %)