• Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
• See Chapter 3 “
Parts listing
” on page 29 to determine which components are consumable, structural, or CRU
parts.
• If an action step is preceded by “(Trained technician only),” that step must be performed only by a trained
technician.
Lit light path
diagnostics LED
Description
Action
Microprocessor
error
The microprocessor has failed or overheated,
or the start microprocessor is missing.
1. Check the Integrated Management Module
II (IMM2) log for more information. See
“Viewing event logs through the Setup
utility” on page 79.
2. If the log shows that a microprocessor is
disabled or that a microprocessor error
has occurred, perform one of the following
actions:
a. (Trained technician only) Reseat the
microprocessor that is indicated by the
lit LED. See “Removing a
microprocessor and heat sink” on page
61 and “Installing a microprocessor
and heat sink” on page 65.
b. (Trained technician only) Replace the
microprocessor that is indicated by the
lit LED. See “Removing a
microprocessor and heat sink” on page
61 and “Installing a microprocessor
and heat sink” on page 65.
NMI (NMI error)
The system board has failed.
1. Replace the blade server cover, reinsert
the blade server in the BladeCenter unit,
and then restart the blade server. Check
the BMC log for information about the
error. See “Using the Setup utility” on page
11.
2. (Trained technician only) Replace the
system-board assembly. See “Removing
the system-board assembly” on page 71
and “Installing the system-board
assembly” on page 71.
SAS storage drive
error
A storage drive has failed.
Run the SAS Attached Disk diagnostic test. If
the drives passes diagnostics but continues to
have a problem, replace the storage drive with
a new one. See “IBM Dynamic System Analysis
Preboot diagnostic program” on page 209.
208
BladeCenter HS23 Blade ServerProblem Determination and Service Guide
Содержание BladeCenter HS23 1929
Страница 1: ...BladeCenter HS23 Blade Server Problem Determination and Service Guide Machine Types 7875 1929 ...
Страница 284: ...268 BladeCenter HS23 Blade ServerProblem Determination and Service Guide ...
Страница 289: ...Taiwan BSMI RoHS declaration Appendix B Notices 273 ...
Страница 290: ...274 BladeCenter HS23 Blade ServerProblem Determination and Service Guide ...
Страница 296: ...280 BladeCenter HS23 Blade ServerProblem Determination and Service Guide ...
Страница 297: ......
Страница 298: ...Part Number 00KC215 Printed in China 1P P N 00KC215 ...
Страница 299: ... 1P00KC215 ...