PRODUCT INFORMATION
INDEX
DATE
Dep. 2
IC-C-D-35-001e D
September 2016
AIR FILTERS
3/4
In GHF High-Flow filter, filtering occurs as follows:
-
Air enters the filter directly through either one or two of the side intake ports, depending on whether the
filter has 1 or 2 filtering cartridges
-
Passes through the filtering cartridge,
-
And finally flows out to the engine through one port with HGM engines and through two ports on the other
engines.
Fig. 4 - General drawing of
Kohler
High Flow two-cartridge filter
To monitor their fouling level, the GHF filters have a mechanical airflow restriction detector Ref. 76.50.319 with a
red-coloured indicator showing up completely when the maximum permissible pressure drop (38 mbar) has
been reached at the filter outlet. In this event, depending on the case, either one or two cartridges need to be
changed. The fouling detector can alternatively be an electric device Ref. 76.50.266 indicating the fouling
condition of the filters by means of a light signal or by transmitting an electric signal to the PLC.
The next figures show exploded views of the GHF air filter.
Fig. 5 - Exploded view of
Kohler
High Flow two-cartridge air filters
COVER
CLAMP
FILTERING ELEMENT
CASING
FOULING
INDICATOR
2.6.7
O&M_2.002211.810_A_10_2016