PRODUCT INFORMATION
INDEX
DATE
Dep. 2
IO-G-M-33-010e
June 2013
INSTALLATION AND OPERATION MANUAL - GIS IGNITION UNIT
DISPLAY
6/14
3.1. READING PARAMETERS
The following briefly explains each of the screen views where data is displayed on the ignition unit:
3.1.1. Overview
This view shows global operating parameters
Fig. 7 – Menu Overview
-
Pick up
: the green status display indicates that pickup signals are being recorded (engine running). If no
signal is detected, the LED remains grey.
-
Ignition Output
: we get different information on the ignition outputs depending on the colour:Grey: the
firing is not active
o
Green: There are no misfires. Everything is working correctly.
o
Yellow: There were previously misfires, but currently there are no more misfires.
o
Red: There are misfires.
Further details on the information this led provides can be found in the
Ignition
view.
-
Ignition Enabled:
This LED indicates whether the ignition unit has received a spark enabled command or
not.
o
Grey: the firing is not activated
o
Green. The firing is activated
-
System
: this LED displays the system status. Equivalent to Status LED on the front of the ignition unit:
o
Grey: the display is not communicating with the ignition unit (the ignition unit is not powered on,
the unit-screen communication is not working...)
o
Green: the ignition unit is recording no errors.
o
Yellow. The ignition unit is giving warnings/alerts (which do not lead to stopping the unit)
o
Red: There are errors, which lead to shut down.
-
Speed:
the pointer shows the engine speed.
-
Ignition Time:
shows the global timing of the engine.
3.1.2.
Timing
This view provides information on how to calculate the ignition timing the engine operates on.
4.1.30
O&M_2.002211.810_A_10_2016