GAS ENGINES – PRESSURE LOSSES AND FLOWRATES
4/7
3.3 AUXILIARY COOLING CIRCUIT. SINGLE-STAGE AIRCOOLER
Engine
Speed Temperature Minimum
Flowrate
Delta P
K
[rpm] [ºC] [m
3
/h] [bar]
SFGLD/SFGRD/SFGM180
1200/1500
55
15
0.42 1.86·10
-3
80 0.43
1.89·10
-3
1800
55
20
0.74 1.86·10
-3
80 0.76
1.89·10
-3
SFGLD/SFGRD/SFGM240
1200 55
15
0.43
1.89·10
-3
1500
40 – 55
20
0.76 1.89·10
-3
80 0.64
1.61·10
-3
1800
55
25
1.18 1.89·10
-3
80 1.01
1.61·10
-3
SFGLD360
1200
55 15
0.25
1.09·10
-3
1500
40 – 55 (90 Main C)
20
0.44 1.09·10
-3
55 (120 Main C)
0.45 1.13·10
-3
80 (90 Main C)
80 (120 Main C)
0.46
1.16·10
-3
1800
55 (90 Main C)
25
0.68 1.09·10
-3
80 (90 Main C)
0.71
1.13·10
-3
80 (90 Main C)
0.71
80 (120 Main C)
0.73
1.16·10
-3
SFGLD480
1200
55 15
0.25
1.13·10
-3
1500
40 – 55 (90 Main C)
20
0.45 1.13·10
-3
55 (120 Main C)
0.46
1.16·10
-3
80 0.47
1.18·10
-3
1800
55
25
0.71 1.13·10
-3
80 0.74
1.18·10
-3
SFGLD560
1200
55 15
0.25
1.13·10
-3
1500
32 – 55
25
0.71
2.2.12