PRODUCT INFORMATION
INDEX
DATE
Dep. 2
IT-G-A-20-007e I
May 2015
GAS ENGINES – PRESSURE LOSSES AND FLOWRATES
3/7
3. MINIMUM FLOWRATES FOR SFGLD / SFGRD / SFGM ENGINES
3.1 MAIN COOLING CIRCUIT – TWO CIRCUITS
Engine
Speed
Minimum flowrate
Delta P
K
[rpm] [m
3
/h] [bar]
SFGLD/SFGRD/SFGM180
1200 20
0.18
4.5·10
-4
1500 25
0.28
1800 30
0.41
SFGLD/SFGRD/SFGM 240
1200 25
0.21
3.3·10
-4
1500 30
0.30
1800 40
0.53
SFGLD/SFGRD/SFGM 360
1200 40
0.16
1.0·10
-4
1500 50
0.25
1800 60
0.36
SFGLD/SFGRD/SFGM 480
1200 50
0.28
1.1·10
-4
1500 60
0.40
1800 80
0.70
SFGLD/SFGRD SFGM /560
1200 60
0.40
1500 70
0.54
1800 75
0.62
3.2 MAIN COOLING CIRCUIT – ONE CIRCUIT
Engine
Speed
Minimum flowrate
Delta P
K
[rpm] [m
3
/h] [bar]
SFGLD 180
1800 40 0,43
2,7·10
-4
SFGLD 240
1800 50 0,30
1,2·10
-4
SFGLD 360
1800 60 0,14
3,9·10
-5
SFGLD 480
1800 80 0,25
3,9·10
-5
SFGLD 560
1800 88 0,30
3,9·10
-5
2.2.11
O&M_2.002211.810_A_10_2016