EMISSIONS - RELATED INSTALLATION INSTRUCTIONS
2/5
- The exhaust pipeline shall be secured by means of collars through which it can slide and properly
distributed fixed anchorage points.
- The exhaust pipeline and silencer shall be protected and heat-insulated to avoid big heat radiations into the
engine room and the subsequent reduction in the engine performance.
- The exhaust pipeline must be laid for each engine individually. Never put together the gas outlets of various
engines in a single collector.
- For completion of the exhaust pipeline, there must be a condensate trap installed at the lower end of the
last vertical run of exhaust pipe as well as one draining valve (
see Figure 1
).
A
Inner Diameter
D
10 mm (0.39 inch)
B
Exhaust Flexible Diameter
E 30º
(86ºF)
C
20 mm (0.78 inch)
n
A
Fig. 1 – “V” Engine Installation of Exhaust Pipeline
ALTERNATIVES TO PREVENT
WATER INFILTRATIONS
SILENCER
FLEXIBLE
SLIDING FIXING
POINT
FLEXIBLE
FLEXIBLE
DIAMETER AS PER TABLE 1
CONDENSATE
TRAP
DRAINING VALVE