PRODUCT INFORMATION
INDEX
DATE
Dep. 2
IO-G-M-00-019e G
January 2016
MAINTENANCE OF NATURAL GAS ENGINE SFGLD
STAND-BY
4/6
Job Interval
Job
Description
E0
250 h
or
6 months
- Analyse waste oil
- Check and refill additive level in coolant
E1
500 h
or
once a year
- Change oil
KOHLER
MOTOROIL (oil sump and cooler)
- Change oil filters
- Clean the oil centrifuge filter, film-thickness measurement and change
the paper filter
- Clean the metallic sponge of the oil purifier
- Measure crankcase pressure
- Check air/fuel ratio
- Adjust
air/fuel ratio to full load (*), if necessary
- Inspect the air filters
- Adjustment of rocker arms and valve lifters. Measure valve height
- Verify the ignition timing
- Check battery and starter connections
- Inspection of
high voltage wires of the ignition system
- Change the filter of crankcase gases recirculation system and clean this circuit (*
A
*)
E2
1,500 h
or
3 years
- Check gas filters
- Change hoses and clamps.
- Test thermostats of coolant circuit.
- Test control and safety devices: temperature and pressure switches and probes
- Check damper temperature
- Change air filters
- Check gaskets in the rocker arm covers
- Disassemble, clean and adjust all the speed and ignition pick-ups
- Measure the exhaust back-pressure
- Change coolant
- Verify the tightening torque of knocking sensors on stud head (20 Nm)
- Check axial and Radial allowance of turbochargers
NOTE
- The spark plugs change must be made attending the IO-G-M-33-007 product information.
*It is recommended cylinder endoscope revision and compression test when the spark-plug change
- Ask
Kohler
to use another oil that it is not
KOHLER
MOTOROIL.
5.1.16
O&M_2.002211.810_A_10_2016