2-14
KLP-HV 031308
2.7.9
ANALOG I/O CONNECTIONS
The Analog I/O Port connector, located on the rear panel of the KLP power supply (see Figure
2-2), provides access for all analog programming inputs and status signal outputs. In addition,
an external trigger input is available for use with SCPI *TRG and TRIG commands. Refer to
Table 2-7 for analog I/O programming signal pin assignments and descriptions.
These signals must be protected from radiated and conducted noise as well as from physical
contact with non-valid driving sources. The following subsections address specific programming
signal applications; in general, however, when accessing this connector from distant locations
or high-noise environments, it is recommended that a shielded cable be used, with the shield
terminated to the system's single point ground.
a. Analog Programming Enable (ANALOG_CTRL)
Connect pin 12 (Analog Control) to pin 9, 11, 13, or 15 (ground) to enable analog I/O pro-
gramming.
b. External Voltage and Current Programming (V_Ref and C_Ref)
Twist the voltage programming signal V_Ref (pin 3), Current Programming signal C_Ref (pin
1) and ground (pin 9, 11, 13, or 15). Configure Analog I/O switch positions 1 and 2 to use
either voltage or resistance as the programming source. Factory default for full scale output
is 10V or 10 Kohms (see par. 4.3.3 to set lower values for full scale output).
c. Voltage and Current Readback (VOLT_RBACK and CURR_RBACK)
Twist the voltage readback signal VOLT_RBACK (pin 6), Current readback signal
CURR_RBACK (pin 7) together with ground (pin 9, 11, 13, or 15). Full scale readback volt-
ages are identical to selected full scale programming voltages (see PAR. 4.3.3).
d. Remote Inhibit (REM_INH)
Twist remote inhibit (pin 8) together with ground (pin 9, 11, 13, or 15). See PAR. 3.2.13.5.1 to
configure active high or low and PAR. 3.4.1 to enable/disable the output using remote inhibit.
e. Fault Connections (RELAY_NC, RELAY_COM, RELAY_NO
It is recommended that normally open and normally closed relay signals RELAY_NC (pin 10)
and/or RELAY_NO (pin 2), respectively, be twisted together with RELAY_COM (pin 4) as
needed to eliminate noise pickup. See PAR. 3.2.13.3 to configure internal relay.
f. External Trigger (EXT_TRIG)
External Trigger may be used with the SCPI TRIG commands (see KLP Developer’s Guide)
during digital remote operation. For noise suppression it is recommended that wires from
EXT_TRIG, pin 14 and ground (pin 9, 11, 13, or 15) be twisted together.
2.8
DIGITAL CONNECTIONS
The following paragraphs describe the connections required to use the GPIB, RS 232 [-1200
Models only] or LAN [-1.2K models only] ports for remote control of the unit.
2.8.1
GPIB CONNECTIONS
Your computer must have a GPIB interface card installed. Connect the power supply to the
computer’s GPIB interface card. Use a standard GPIB interface cable at the GPIB port on the
rear panel (See Figure 2-2). Refer to Table 2-3 for GPIB port pin assignments. Refer to PAR.
3.2.9 to change the default GPIB address (6) from the front panel.
Содержание KLP 10-150-1.2K
Страница 2: ......
Страница 6: ......
Страница 12: ...vi KLP031308 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 18: ...1 6 KLP 031308 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 19: ...KLP 031308 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 24: ......
Страница 27: ...KLP HV 031308 2 3 FIGURE 2 2 KLP SERIES REAR PANEL SWITCH AND CONNECTORS...
Страница 40: ......