KLP031308
3-9
3.2.11.1
CONFIGURE POWER SUPPLY AS MASTER [-1200 MODELS ONLY]
1. Turn power on. If the unit comes up in setpoint mode (see PAR. 3.2.4), tap either the
CUR-
RENT
or
VOLTAGE
controls to take the unit out of setpoint mode (status display goes from
SET
to blank).
2. Using a thin tool (e.g., a paper clip), press the
FUNCTION
switch once until the status dis-
play reads
VIRT
. Rotate either the
CURRENT
or
VOLTAGE
control until the display reads
M/S
.
3. Tap the
DC OUTPUT
switch once.
• The status display reads either
SERI
(series) or
PARA
(parallel).
• The
DC VOLTS
display shows the number assigned to the unit (1 = master, 2 or above
= slave).
• The
DC AMPERES
display shows the maximum number of units in the configuration.
• The factory default is standalone operation (
DC VOLTS
and
DC AMPERES
show
1
).
4. To change the configuration tap the
DC OUTPUT
switch once. The
DC VOLTS
and
DC
AMPERES
start blinking.
• Specify either
SERI
(series configuration for higher voltage) or
PARA
(parallel configura-
tion for higher current) using either the
VOLTAGE
or
CURRENT
control by
holding in
and rotating the control. Both connected units must be set the same, either
SERI
or
PARA
.
• Specify the total number of units in the configuration to 2 by rotating the
CURRENT
con-
trol.
• Specify the unit number to be assigned (1 = master) by rotating the
VOLTAGE
control.
5. Press
DC OUTPUT
to accept the displayed settings. The unit briefly flashes
WAIT
, then
restarts with the new settings; press
FUNCTION
to abort without changing the settings.
NOTE: Until both units are configured properly, the displays will cycle as follows: status display
will flash
E241
(hardware error), then
DC VOLTS,
status display
and
DC AMPERES
flash
x
OF
y
where
x
= unit number and
y
= total number of units, the status display
flashes the type of connection
SERI
(series) or
PARA
(parallel).
3.2.11.2
CONFIGURE POWER SUPPLY AS SLAVE [-1200 MODELS ONLY]
1. Turn power on. If the unit comes up in setpoint mode (see PAR. 3.2.4), tap either the
CUR-
RENT
or
VOLTAGE
control to take the unit out of setpoint mode (status display goes from
SET
to blank).
2. Using a thin tool (e.g., a paper clip), press the
FUNCTION
switch once until the status dis-
play reads
VIRT
. Rotate either the
CURRENT
or
VOLTAGE
control until the display reads
M/S
.
3. Tap the
DC OUTPUT
switch once.
• The status display reads either
SERI
(series) or
PARA
(parallel).
Содержание KLP 10-150-1.2K
Страница 2: ......
Страница 6: ......
Страница 12: ...vi KLP031308 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 18: ...1 6 KLP 031308 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 19: ...KLP 031308 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 24: ......
Страница 27: ...KLP HV 031308 2 3 FIGURE 2 2 KLP SERIES REAR PANEL SWITCH AND CONNECTORS...
Страница 40: ......