3-26
KLP031308
ture. These settings are cleared when a calibration is performed. Click
SAVE/RECALL
to open
the Save/Recall Dialog Box (Figure 3-9).
FIGURE 3-9. SAVE/RECALL DIALOG BOX
NOTE: When the SAVE/RECALL tab is initially selected, parameters for all locations appear
as empty even when there are values stored from previous sessions. Click the
Pre-
view
button first to avoid overwriting existing data.
•
To view currently stored settings:
Enter a location (1 to 40) in the box between
Save @
and
Preview
buttons, then click
Preview
button.
•
To change currently stored settings:
Enter a location (1 to 40) in the box between
Save @
and
Preview
buttons, then click
Preview
button. Modify the settings and click
Save @
button
to save the modified settings.
•
To save the active settings:
Enter the desired location (1 to 40) in the
LOCATION
box and
click
Save State
button to save the active settings. Only the parameters shown in Figure 3-7
can be saved.
•
To save user-determined settings:
Enter location (1 to 40) in the box between
Save @
and
Preview
buttons. Enter desired values for Voltage, Current, Overvoltage Protection and
Overcurrent protection. Select whether the output is to be on or off, then click
Save @
button
to save the settings
•
To Recall settings:
Enter the desired location in the
LOCATION
field and click
Recall State
to set previously stored settings as the active settings.
If a virtual model setting is changed, and a stored setting is outside the range established by the
new virtual model, the data set is not loaded; although there is no indication on the web page,
the Status Display of the power supply will flash E221, "Settings conflict.
Содержание KLP 10-150-1.2K
Страница 2: ......
Страница 6: ......
Страница 12: ...vi KLP031308 FIGURE 1 1 KLP SERIES POWER SUPPLY...
Страница 18: ...1 6 KLP 031308 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 R DWG MECH 3010266...
Страница 19: ...KLP 031308 1 7 FIGURE 1 3 KLP SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2...
Страница 24: ......
Страница 27: ...KLP HV 031308 2 3 FIGURE 2 2 KLP SERIES REAR PANEL SWITCH AND CONNECTORS...
Страница 40: ......