10.5.4.4. Smartmeter - Smartmeter
In the tab "Smartmeter" the Smart Metering devices are managed, which are connected to the PowerManager.
In the overview you will see already learned devices. With "+" you can add more smart meters.
The info button ("i") also gives you additional information such as the device address and the current firmware
version.
Teach-in of new Smartmeters
To teach in a new smart metering device, click on the "+". Then select the counter type and the number of
phases.
In addition, a name must be assigned and the smartmeter address entered which is similar to the serial number
printed on the Smartmeter.
Then click on the arrow next to the Smartmeter address. This starts the search for new smart meters on the
PowerManager.
On the smartmeter, the teach-in button "LEARN" must then be pressed and held down until the "INFO" LED
flashes permanently. This takes about 20 seconds.
The smartmeter should then be recognized after about 10-20 seconds and added to the list of already
configured smart meters.
Then continue with the configuration of the device by clicking on the edit pen.
Page
(07-2018, subject to change)
kentix.com
97
NOTICE!
Note that to learn new Smart Metering devices, you must be within range of the respective PowerManager
(up to 30m).