Navigation
Dashboard
- Starting page with measurement table, graphic history, logbook
Sensors
- Configuration of sensor thresholds, alarm behavior and motion detection
User
- User configuration (Login, E-Mail)
Configuration
- Basic settings, network and notification settings
System
- System log book, configuration management (backup / restore),
firmware update, SD card management
Logout
- User logout
6.6.3. Sensors (sensors and alarming)
In the following settings you can set the limit and action values for the alerting.
When an alarm is triggered, an e-mail will be sent to the configured persons and the internal buzzer is activated.
Sensor-Temperature, Humidity, Dew-point
Set the alarm limit values. Alarm will be triggered when the measurements undershot or exceeded the limits.
The temperature hysteresis is 1°C, humidity hysteresis 1%.
The dew-point is calculated with the current temperature and the relative humidity from the sensor.
If the room temperature approximates to the difference of the set dew-point hysteresis (2°C default) an alarm
will be triggered. Systems and devices can lead to condensation, when the dew point temperature approximates
the room temperature.
Sensor-Carbon Monoxide
Alarm settings for the Carbon Monoxide. The sensitivity can be set from 0% to 100% and will be triggered by
exceeding. CO is measured from about 10ppm. There is no exact measurement of the CO content. The
measurement is construed to the highest sensitivity and can be changed slightly in the adjustment.
Carbon Monoxide concentrations like they emerge in fires are detected even at 100% setting.
10%: Minimal concentration of around 20-50ppm lead to an alarm trigger.
100%: Concentrations of 200ppm and more lead to an alarm trigger.
Sensor-Motion
Limit value for the integrated PIR (passive infra-rot) motion detection. It is triggered when exceeded. Objects
which have a temperature difference of about 4°C to the environment temperature and which are bigger than
250x400mm will be detected. For a safe detection of persons, the value should be in the range of 30-50%.
The detection range is about 100°.
Sensor-Vibration
Alarm settings for the sensitivity of the internal vibration sensor. The sensitivity can be adjusted in 3 levels.
If necessary the vibration sensor can also be completely turned of.
Ext. alarm sensors
The MultiSensor has two configureable alarm inputs. At this alarm inputs external signaling devices can be
plugged (e.g leakage sensors, door contacts or malfunction messages from external devices). The trigger is set
by a potential free contact (opener). The trigger logic can be set to Open or Closed.
Ext. alarm output
With this output external devices or signals can be switched.
An additional adapter (KIO3) is required for use.
The description can be found later in this manual.