Connection example 2: Daisy chaining leakage sensors
It is possible to to chain up to 5 leakage sensors together and connect them to a Kentix system jack via
standard patch cables. Therefore they can be patched into structured wirings. The combined cable lenth should
not exceed 50m. It is important to code the according sensors as intermediate or end device.For this purpose a
micro switch is located inside the casing.
Page
(07-2018, subject to change)
kentix.com
43
IN
OUT
IN
IN
OUT
OUT
MID
MID
END
KENTIX system jack
Max. 5 sensors
chainable
Combined cable length
max. 50m
Setting of the
detection sensitivity
(Default position: 1 o‘clock)
Coding of
the chain position
L
e
a
ka
g
e
Se
n
so
r
Accessories