-98-
P9.48
Fault protection action
selection 2
One’s
place
Encoder fault (20=E.PG1)
000
00
☆
Coast to stop
0
Switch to V/F mode and stop according
to stop mode
1
Switch to V/F mode and continue to run
2
Ten’s
place
EEPROM fault (21=E.EEP)
Coast to stop
0
Stop according to stop mode
1
Hundr
ed’s
place
reserved
Thous
and's
place
Motor overheat (45= E.oHt)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten
thous
and's
place
Accumulative running time
reached (26= E.ArA)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
P9.49
Fault protection action
selection 3
One’s
place
User defined fault 1 (27=
E.USt1)
000
00
☆
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Ten’s
place
User defined fault 2(28= E.USt2)
Coast to stop
0
Stop according to stop mode
1
Continue to run
2
Hundr
ed’s
place
Accumulative power-on time
reached (29= E.APA)
Содержание DLB1-0D40S2G
Страница 10: ...10 Graph 1 5 5 5 7 5KW product outline dimensions Graph 1 611 18 5KW product outline dimensions...
Страница 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Страница 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Страница 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Страница 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Страница 159: ...159...