-89-
P8.36
Output over-current
threshold
0.0%(No detection )
0.1%~300.0%( motorrated current)
200.0%
☆
P8.37
Output over-current
detection delay time
0.00s~600.00s
0.00s
☆
If the output current of the Inverter is equal to or higher than the overcurrent threshold and the
duration exceeds the detection delay time, the corresponding DO becomes ON. The output
overcurrent detection function is shown in the graph above.
Output
current
Output
over-current
signal
t
t
P8.36
ON
P8.37
Zero current
detection
signal
t
t
ON
P8.34
P8.35
Output
current