-60-
It is the most commonly used two-line mode, in which the forward/reverse rotation of the motor is
decided by DI1x and DIy. The parameters are set as below:
Value
Function
Description
DIx
1
Forward
operation(FWD)
DIy
2
Reverse
operation(REV)
As shown in the below figure, when only K1 is ON, the Inverter instructs forward rotation. When only
K2 is ON, the Inverter instructs reverse rotation. When K1 and K2 are ON or OFF simultaneously, the
Inverter stops.
K1
K2
Operation
0
0
Stop
0
1
REV
1
0
FWD
1
1
Stop
1:Two-line mode 2;
DI
x
RUN
enabl
ed
DI
y
FWD
or
REV
COM
K1
K2
In this mode, DIx is enable terminal, and DIy terminal decides operation direction .
Value
Function
Description
DIx
1
Forward
operation(FWD)
DIy
2
Reverse
operation(REV)
0: invalid; 1: valid.
K1
K2
Operation
0
0
Stop
0
1
Stop
1
0
FWD
1
1
REV
Содержание DLB1-0D40S2G
Страница 10: ...10 Graph 1 5 5 5 7 5KW product outline dimensions Graph 1 611 18 5KW product outline dimensions...
Страница 11: ...11 Graph 1 722 30KW product outline dimensions Graph 1 837 55KW product outline dimensions...
Страница 12: ...12 Graph 1 875 110KW product outline dimensions Graph 1 9 132 160KW product outline dimensions...
Страница 14: ...14 2 Wirings 2 1 Standard wiring diagrams Graph 2 8 0 4 18 5KW inverter wiring diagram...
Страница 15: ...15 Graph 2 922 400KW inverter wiring diagram...
Страница 159: ...159...