5:Three-line mode 3;
COM
SB2
SB1
DI
x
(
FWD)
DI
y
(
REV)
DI
n
RUN
enabl
ed
SB3
SB1: Stop button
SB2: FWD button
SB3: REV button
In this mode, the earlier valid terminals have priorities.
Value
Function
Description
DIx
1
Forward
operation(FWD)
DIy
2
Reverse
operation(REV)
DIn
3
RUN enabled
0: invalid; 1: valid; X: random.
SB1
SB2
SB3
Operation
0
X
X
Stop
1
1
0
FWD
1
0
1
REV
1
1
0->1
FWD
1
0->1
1
REV
Ten’s place:
To determine priorities between operation command and JOG.
P4.12
Terminal UP/DOW N rate
0.01Hz/s~65.535Hz/s
1.00Hz/s
☆
It is used to adjust the rate of change of frequency when the frequency is adjusted by means of
terminal UP/DOW N.
•
If P0.22 (Frequency reference resolution) is 2, the setting range is 0.001-65.535 Hz/s.
•
If P0.22 (Frequency reference resolution) is 1, the setting range is 0.01-655.35 Hz/s.