89
item Controller BL 1-04 /C
― Product manual
37-5
Sercos: unknown operation
mode selected
Check the settings for the operating modes in the IDNs S-0-0032 to S-0-0035.
37-6
Sercos: T3 invalid
Increase the baud rate. Shift T3 manually.
37-7
Sercos III: communication
error
Please contact the Technical Support team.
Group 38: Sercos
38-0
Sercos: SERCON Status
event
No measures required.
38-1
Sercos: no module present
Sercos has been activated, but no technology module has been inserted.
Is the technology module correctly inserted?Is the technology module defecti
-
ve?Replace the technology module. Please contact the Technical Support team.
38-2
Sercos: defective module
Replace the technology module.
Please contact the Technical Support team.
38-3
Sercos: S-0-0127: invalid
data in S-0-0021
Check the configuration (cyclic data for MDT and AT).
Check the time slot calculation by the master.
38-4
Sercos: S-0-0127: impermis
-
sible IDNs in AT or MDT
Check the configuration for the cyclic data transfer.
38-5
Sercos: S-0-0128: invalid
data in S-0-0022
Check the scaling settings.
Check the operating mode settings. Check the internal/external angle encoder settings.
38-6
Sercos: S-0-0128: incorrect
scaling
Check the scaling settings.
38-7
Sercos: invalid IDN in S-0-
0026 / S-0-0027
Check the configuration of the signal status and signal control word (S-
0-0026/S-0-0027).
38-8
Sercos: conversion error
Check the scaling settings.
Please contact the Technical Support team.
38-9
Sercos: SERCON 410b
mode active
Replace the technology module.
Please contact the Technical Support team.
Group 39: Sercos
39-0
Sercos: list S-0-0370:
incorrect configuration of
the MDT data container
Please contact the Technical Support team.
39-1
Sercos: list S-0-0371: incor
-
rect configuration of the AT
data container
39-2
Sercos: error in the cyclic
channel MDT
39-3
Sercos: error in the cyclic
channel AT
39-4
Sercos: error in the cyclic
data container MDT
39-5
Sercos: error in the cyclic
data container AT