item Controller BL 1-04 /C
― Product manual
48
Response time until power output stage inactive and maximum OSSD test pulse duration
Characteristic
Value
Input voltage (STOA/STOB) 19.2 V
24 V
28.8 V
Typical response time
2 ms
3 ms
4 ms
Max. test pulse duration
(OSSD)
0.5 ms
1 ms
1.5 ms
The maximum response time t
STOAB/OFF
is described in section 8.11.2.1 Time response of the STO activation during operation
with a restart on page 48.
8.11.2 Time response
INFO
Equal inputs in terms of their functionality
The inputs STOA and STOB are absolutely equal in terms of their functionality, which is why the switching sequence of STOA/
STOB is interchangeable in all of the diagrams.
8.11.2.1 Time response of the STO activation during operation with a restart
The illustration shows the time response starting with the disconnection of the control voltage at STOA/B and the sequence
that is necessary for restarting the device.
▪ The actuation of the holding brake is realised via the basic device and not in a safety-oriented manner.
▪ The illustration shows the coasting of the motor regardless of the activation/deactivation of the brake
▪ The setpoint will not be enabled until the holding brake delay TF has elapsed.
▪ An error will be issued as the STO inputs are deactivated while the output stage is active. It is not included in the drawing.