Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
31
Opt
idr
ive
P2
Par
ame
ter
Se
t Ov
er
view
1
P1-13 = 5
P1-13 = 6
Open
Closed
Open
Closed
Stop
Run
Stop
Run
Forward Rotation
Reverse Rotation
Forward Rotation
Reverse Rotation
Selected Speed
Reference
Analog Input 2
Speed Reference
Selected Speed
Reference
Preset Speed 1
Analog Input 1
Analog Input 1
Analog Input 2
External Trip
Safe Torque OFF inputs
Contacts must be closed to operate drive
Safe Torque OFF inputs
Contacts must be closed to operate drive
P1-13 = 7
P1-13 = 8
Open
Closed
Open
Closed
Stop
Run
Stop
Run
Forward Rotation
Reverse Rotation
Forward Rotation
Reverse Rotation
Preset Speed Reference Selected as
follows:-
Preset Speed Reference Selected as
follows:-
DIN3
AIN1
Preset
DIN3
AIN1
Preset
OFF
OFF
P2-01
OFF
OFF
P2-01
ON
OFF
P2-02
ON
OFF
P2-02
OFF
ON
P2-03
OFF
ON
P2-03
ON
ON
P2-04
ON
ON
P2-04
External Trip
Decel ramp 1
(P1-04)
Decel Ramp 2
(P2-25)
Safe Torque OFF inputs
Contacts must be closed to operate drive
Safe Torque OFF inputs
Contacts must be closed to operate drive
P1-13 = 9
P1-13 = 10
Open
Closed
Open
Closed
Stop
Run
Stop
Run
Forward Rotation
Reverse Rotation
Forward Rotation
Reverse Rotation
Preset Speed Reference Selected as
follows:-
Increase Speed
1)
DIN3
AIN1
Preset
OFF
OFF
P2-01
Decrease Speed
1)
ON
OFF
P2-02
OFF
ON
P2-03
ON
ON
P2-04
Selected Speed
Reference
Preset Speeds
Reference 1 - 4
Selected Speed
Reference
Preset Speed 1
Safe Torque OFF inputs
Contacts must be closed to operate drive
Safe Torque OFF inputs
Contacts must be closed to operate drive
1)
Increase / Decrease speed function only works if the Selected Speed
reference is the Motorised Pot (P1-12 = 1 or 2)
P1-13 = 11
P1-13 = 12
Open
Closed
Open
Closed
Stop
Run Forward
Stop
Run Forward
Stop
Run Reverse
Stop
Run Reverse
Selected Speed
Reference
Preset Speed
Reference
Preset Speed Reference Selected as
follows:-
DIN3
AIN1
AIN2
Preset
Analog Input 1
OFF
OFF
OFF
P2-01
ON
OFF
OFF
P2-02
OFF
ON
OFF
P2-03
ON
ON
OFF
P2-04
OFF
OFF
ON
P2-05
Preset Speed 1
Preset Speed 2
ON
OFF
ON
P2-06
Safe Torque OFF inputs
Contacts must be closed to operate drive
OFF
ON
ON
P2-07
ON
ON
ON
P2-08
Safe Torque OFF inputs
Contacts must be closed to operate drive