Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
27
Opt
idr
iv
e P
2
Par
ame
ter
Se
t Ov
er
view
1
Par
Description
Units
P0-27
Energy Consumption MWh Meter
MWh
Displays the amount of energy consumed by the drive in MWh.
This parameter contains 2 values. The first value, visible when entering the parameter, is the User Resettable MWh meter, which can
be reset by setting P6-23 = 1. The second value cannot be reset by the user, and indicates the energy consumed by the drive when
operating since the date of manufacture.
P0-28
Software Version and Checksum
-
Displays the software version of the drive
P0-29
Drive Type
Displays the type details of the drive
P0-30
Drive Serial Number
Displays the unique serial number of the drive.
P0-31
Drive Lifetime Operating Time
HH:MM:SS
Displays the total operating time of the drive. The first value shown is the number of hours. Pressing the Up key will display the
minutes and seconds.
P0-32
Drive Run Time Since Last Trip (1)
HH:MM:SS
Displays the total operating time of the drive since the last fault occurred. The first value shown is the number of hours. Pressing the
Up key will display the minutes and seconds.
P0-33
Drive Run time Since Last Trip (2)
HH:MM:SS
Displays the total operating time of the drive since the last fault occurred. The first value shown is the number of hours. Pressing the
Up key will display the minutes and seconds.
P0-34
Drive Run Time Since Last Disable
HH:MM:SS
Displays the total operating time of the drive since the last Run command was received. The first value shown is the number of hours.
Pressing the Up key will display the minutes and seconds.
P0-35
Drive Internal Cooling Fan Total Operating Time
HH:MM:SS
Displays the total operating time of the Optidrive internal cooling fans. The first value shown is the number of hours. Pressing the Up
key will display the minutes and seconds. This is used for scheduled maintenance information
P0-36
DC Bus Voltage Log (256ms)
Volts
P0-37
DC Bus Voltage Ripple Log (20ms)
Volts
P0-38
Heatsink Temperature Log (30s)
°C
P0-39
Ambient Temperature Log (30s)
°C
P0-40
Motor Current Log (256ms)
Amps
The above parameters are used to store the history of various measured levels within the drive at various regular time intervals prior
to a trip. The values are frozen when a fault occurs and can be used for diagnostic purposes – see section for further information.
P0-41
Critical Fault Counter – Over Current
-
P0-42
Critical fault counter – Over Voltage
-
P0-43
Critical fault counter – Under Voltage
-
P0-44
Critical fault counter – Over Temperature
-
P0-45
Critical fault counter – Brake Transistor Over Current
-
P0-46
Critical fault counter – Ambient Over Temperature
-
These parameters contain a record of how many times certain critical faults have occurred during a drives operating lifetime. This
provides useful diagnostic data
P0-47
I/O Processor Error Count
-
P0-48
DSP Error Count
-
Displays the relevant internal error count for the drive processors, sueful for diagnostics.
P0-49
Modbus RTU Communication Error Counter
-
This parameter is incremented every time an error occurs on the Modbus RTU communication link. This information can be used for
diagnostic purposes.
P0-50
CAN Open Communication Error Counter
-
This parameter is incremented every time an error occurs on the CAN Open communication link. This information can be used for
diagnostic purposes.
P0-51
PDI Cyclic Data
-
Displays the incoming PDI processor data when a fieldbus interface is connected and operating that supports process data
interchange, useful for fieldbus diagnostics and trouble shooting.
P0-52
PDO Cyclic Data
-
Displays the outgoing PDO processor data when a fieldbus interface is connected and operating that supports process data
interchange, useful for fieldbus diagnostics and trouble shooting.
P0-53
Current Phase U Offset and Ref
-
Index 1 : Reference
Index 2 : Sampled Value
P0-54
Current Phase V Offset and Ref
-
Index 1 : Reference
Index 2 : Sampled Value
P0-56
Brake Max On Time and Duty Cycle
-
Index 1 : Max On Time
Index 2 : Duty