Group 2 : Extended parameter set (Level 2)
Parameter
Number
R/W
Modbus
RTU
Register
Number
CAN
Open
Index
CAN
Open
Sub
Index
Profibus
DP
DeviceNet
EtherNet
IP
EtherCAT
Modbus
TCP
Profinet
IO
Parameter Name
Setting Range
Scaling
Type
P2-01
R/W
201
20C9h
0h
0, 200
A2h, 201, X
A2h, 201, X
20C9h
728
0, 0, 1, 00C9h
Preset speed 1
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-02
R/W
202
20CAh
0h
0, 201
A2h, 202, X
A2h, 202, X
20CAh
729
0, 0, 1, 00CAh
Preset speed 2
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-03
R/W
203
20CBh
0h
0, 202
A2h, 203, X
A2h, 203, X
20CBh
730
0, 0, 1, 00CBh
Preset speed 3
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-04
R/W
204
20CCh
0h
0, 203
A2h, 204, X
A2h, 204, X
20CCh
731
0, 0, 1, 00CCh
Preset speed 4
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-05
R/W
205
20CDh
0h
0, 204
A2h, 205, X
A2h, 205, X
20CDh
732
0, 0, 1, 00CDh
Preset speed 5
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-06
R/W
206
20CEh
0h
0, 205
A2h, 206, X
A2h, 206, X
20CEh
733
0, 0, 1, 00CEh
Preset speed 6
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-07
R/W
207
20CFh
0h
0, 206
A2h, 207, X
A2h, 207, X
20CFh
734
0, 0, 1, 00CFh
Preset speed 7
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-08
R/W
208
20D0h
0h
0, 207
A2h, 208, X
A2h, 208, X
20D0h
735
0, 0, 1, 00D0h
Preset speed 8
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-09
R/W
209
20D1h
0h
0, 208
A2h, 209, X
A2h, 209, X
20D1h
736
0, 0, 1, 00D1h
Skip frequency centre point
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-10
R/W
210
20D2h
0h
0, 209
A2h, 210, X
A2h, 210, X
20D2h
737
0, 0, 1, 00D2h
Skip frequency band
0 to 30000 (Limited by P1-01 Setting)
3000 = 50.0Hz
U16
P2-11
R/W
211
20D3h
0h
0, 210
A2h, 211, X
A2h, 211, X
20D3h
738
0, 0, 1, 00D3h
Analog output 1 function select
Digital Mode (0V or 24V only)
0: Drive running
1: Drive healthy
2: Motor at target speed
3: Motor Speed > 0
4: Motor Speed > limit
5: Motor Current > limit
6: Motor Torque > limit
7: 2
nd
Analog input > limit
(Limit set by P2-18, P2-19)
Analog Mode
8: Speed
9: Current
10: Torque
11: Power
U16
P2-12
R/W
212
20D4h
0h
0, 211
A2h, 212, X
A2h, 212, X
20D4h
739
0, 0, 1, 00D4h
Analog output 1 format
0 = 0…10V
1 = 10…0V
2 = 0-20mA
3 = 20-0mA
4 = 4-20mA
5 = 20-4mA
U16
P2-13
R/W
213
20D5h
0h
0, 212
A2h, 213, X
A2h, 213, X
20D5h
740
0, 0, 1, 00D5h
Analog output 2 function select
Digital Mode (0V or 24V only)
0: Drive running
1: Drive healthy
2: Motor at target speed
3: Motor Speed > 0
4: Motor Speed > limit
5: Motor Current > limit
6: Motor Torque > limit
7: 2
nd
Analog input > limit
(Limit set by P2-18, P2-19)
Analog Mode
8: Speed
9: Current
10: Torque
11: Power
U16
P2-14
R/W
214
20D6h
0h
0, 213
A2h, 214, X
A2h, 214, X
20D6h
741
0, 0, 1, 00D6h
Analog output 2 format
0 = 0…10V
1 = 10…0V
2 = 0-20mA
3 = 20-0mA
4 = 4-20mA
5 = 20-4mA
U16