Optidrive P2 Advanced User Guide Rev 2.00
www.invertekdrives.com
35
Dr
ive
Mo
del
Spe
cifi
c P
ar
am
et
er
Var
ia
tio
n
s
2
2.2.
V/F Mode Voltage Boost Setting Options
230 Volt, 1 Phase Input Models
kW
HP
Default
Maximum
0.75
1
2.5%
30.0%
1.5
2
2.5%
30.0%
2.2
3
2.5%
30.0%
230 Volt, 3 Phase Input Models
kW
HP
Default
Maximum
0.75
1
2.5%
30.0%
1.5
2
2.5%
30.0%
2.2
3
2.5%
30.0%
3
4
2.0%
20.0%
4
5
1.5%
20.0%
5.5
7.5
1.5%
20.0%
7.5
10
1.5%
20.0%
11
15
1.5%
20.0%
15
20
1.0%
20.0%
18.5
25
1.0%
20.0%
22
30
1.0%
15.0%
30
40
1.0%
15.0%
37
50
1.0%
15.0%
45
60
1.0%
15.0%
55
75
0.5%
15.0%
75
100
0.5%
15.0%
90
125
0.5%
15.0%
400 Volt 3 Phase Input Models
kW
HP
Default
Maximum
0.75
1
2.5%
30.0%
1.5
2
2.5%
30.0%
2.2
3
2.5%
30.0%
4
5
2.5%
30.0%
5.5
7.5
2.0%
20.0%
7.5
10
1.5%
20.0%
11
15
1.5%
20.0%
15
20
1.5%
20.0%
18.5
25
1.5%
20.0%
22
30
1.5%
20.0%
30
40
1.0%
20.0%
37
50
1.0%
20.0%
45
60
1.0%
15.0%
55
75
1.0%
15.0%
75
120
1.0%
15.0%
90
150
1.0%
15.0%
110
175
0.5%
15.0%
132
200
0.5%
15.0%
160
250
0.5%
15.0%
200
300
0.2%
10.0%
250
350
0.2%
10.0%
600 Volt 3 Phase Input Models
kW
HP
Default
Maximum
0.75
1
2.5%
30.0%
1.5
2
2.5%
30.0%
2.2
3
2.5%
30.0%
4
5
2.5%
30.0%
5.5
7.5
2.5%
20.0%
7.5
10
2.0%
20.0%
11
15
1.5%
20.0%
15
20
1.0%
20.0%
18.5
25
1.5%
20.0%
22
30
1.5%
20.0%
30
40
1.5%
20.0%
37
50
1.0%
20.0%
45
60
1.0%
20.0%
55
75
1.0%
15.0%
75
120
1.0%
15.0%
90
150
1.0%
15.0%
110
175
1.0%
15.0%