Optidrive P2 Advanced User Guide Revision 2.00
72
www.invertekdrives.com
G
en
er
al Tec
hni
cal
a
n
d P
er
fo
rman
ce Da
ta
8
8.2.2.
400 / 460 Volt Input
Frame
Size
Supply
Voltage
Power
Rating
(kW)
Input
Current
(A)
iTHD
(%)
AC
Line
Choke
Input
Current
(A)
iTHD
(%)
Output
Current
(A)
2
400V, 3ph
0.75
3.5
177.8
OPT-2-L3006-20
2.7
92.5
2.2
1.5
5.6
155.0
OPT-2-L3006-20
4.5
64.5
4.1
2.2
7.5
147.2
OPT-2-L3006-20
5.5
64.5
5.8
4.0
11.5
124.3
OPT-2-L3010-20
8.9
47.3
9.5
3
400V, 3ph
5.5
17.2
126.3
OPT-2-L3036-20
14.5
53.6
14
7.5
21.8
115.5
OPT-2-L3036-20
17.7
47.3
18
11
27.5
102.7
OPT-2-L3036-20
21.9
43.6
24
4
400V, 3ph
11
28.0
117.0
OPT-2-L3036-20
21.9
43.6
24
15
34.2
108.0
OPT-2-L3036-20
28.1
47.3
30
18.5
44.1
104.0
OPT-2-L3050-20
35.4
39.4
39
22
51.9
99.1
OPT-2-L3050-20
41.5
37
46
5
400V, 3ph
30
66.1
84.8
OPT-2-L3090-20
56.3
43.6
61
37
77.3
88.8
OPT-2-L3090-20
65.4
39.4
72
6
400V, 3ph
45
102.7
93.8
OPT-2-L3090-20
91.6
64.5
90
55
126.4
88.8
OPT-2-L3200-00
112
64.5
110
75
164.7
77.2
OPT-2-L3200-00
147.4
53.6
150
90
192.1
72.6
OPT-2-L3200-00
172.4
47.3
180
7
400V, 3ph
110
210.8
57.5
OPT-2-L3200-00
208.1
64.5
202
132
241.0
50.5
OPT-2-L3300-00
238.6
53.6
240
160
299.0
44.8
OPT-2-L3300-00
296.2
47.3
302
8
400V, 3ph
200
377.2
56.3
OPT-2-L3500-00
376.6
42.1
370
250
458.7
56.3
OPT-2-L34500-00
429.4
42.1
450
The data above is provided to show typical values. Results measured at the point of installation may vary according to the installation site and
load conditions Test results are measured under the following conditions :-
400 Volt RMS AC Supply Voltage
Operating IE2 motor with matching power rating according to the drive
Operated at full rated output current capacity