Configurations
Function configuration of the inputs and outputs
73
5.5
Function configuration of the inputs and
outputs
Configuration of the inputs and outputs (default setting) .............................................................73
System variables ..........................................................................................................................73
Configure inputs ...........................................................................................................................74
7308
For specific in- and outputs, additional diagnostic functions can be activated. So the corresponding
input and output signal can be monitored and the application program can react in case of a fault.
Depending on the input and output, certain marginal conditions must be taken into account when
using the diagnosis:
It must be checked by means of the data sheet if the device used has the described input and
output groups.
Constants are predefined (e.g. IN_DIGITAL_H) in the device libraries (ifm_CRnnnn_Vx.LIB) for
the configuration of the inputs and outputs.
For details
Possible operating modes inputs / outputs
(
→
).
5.5.1
Configuration of the inputs and outputs (default setting)
2249
All inputs and outputs are in the binary mode (positive switching!) when delivered.
The diagnostic function is not active.
OUT_OVERLOAD_PROTECTION is active.
5.5.2
System variables
2252
All system variables (
Annex
(
→
page
)) have defined addresses which cannot be shifted.
Indication of the selected I/O configuration via mode bytes
To indicate and process a watchdog error or causes of a new start the system variable
LAST_RESET is set.