Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
82
of 84
8.2
Physical Specifications
Table 33. Physical Specifications
Parameters
Configuration
Output Grounding
Power Modules are floating, may be connected with
Positive or Negative ground
7
Alarm Output
Form-C contact, 0.5 A 60 VDC max
DC Connectors: (Output, Battery,
DC-DC Converter Module)
Bus Bar, 5/16-inch bolt hole
Load Distribution Module (LDM)
Connectors
8-terminal cage clamp style, 12
–22 AWG,
0.51 Nm max torque
Alarm Output Connector
3-pin removable plug, cage clamp type 16
–24 AWG
Alarm Input, Bat temp sense
Connector
7-pin removable plug, cage clamp type 16
–24 AWG
AC Input Connector
3-pin removable plug, cage clamp type 8
–22 AWG
Operating Temperature Range
−30 to +60°C
Storage Temperature Range
−45 to +85°C
Humidity
(Operating) 10
–90% (non-condensing)
(Storage) 5
–95% (non-condensing)
Cooling
Load controlled fan on Power Modules
7
BMMD and LDM modules are available in positive (-48 volts) or negative (+12/24 volts) ground
configuration. Specify at time of ordering.
8.3
Regulatory Specification
Table 34. Regulatory Compliance
Category
Certification
Safety, EMC-Emissions,
EMC-Immunity, RoHS
(700 W)
UL/CSA60950-1, UL/CSA 62368-1, ICES-003, FCC Part
15/B, EN 61000-6-2, EN 61000-6-3, EIC 61000-4-5 and
RoHS
Safety, EMC-Emissions,
EMC-Immunity, RoHS
(1,500 W)
UL/CSA60950-1, UL/CSA 62368-1, ICES-003, EN55032,
EN 61000-3-2, EN 61000-3-3, EIC 61000-4-5 and RoHS
8.4
Mechanical Specifications
Table 35. Dimension and Weight
Physical Property
Value
Dimension - L x W x H
15.7 x 19.0 x 3.5 in. (398 x 483 x 89 mm)
Weight
32 lbs. (14.5 kg)
8
maximum
8
Weight of unit as shipped with BMMD, LDM and DC-DC Converter Module. No Power Modules.