Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
81
of 84
Parameters
Power
Chassis
ICT
700-
24PM
ICT
700-
48PM
ICT
1500-
24PM
ICT
1500-
48PM
Output Current (continuous)
(230 VAC)
270 A
25 A
12.5 A
54 A
27 A
Output Current (continuous)
(115 VAC)
135 A
25 A
12.5 A
32 A
16 A
Output Derating
2% / °C (above 50°C)
Efficiency (peak)
-
91%
93%
94%
95%
Output Noise (max mV
rms
)
-
30 mV
rms
60 mV
rms
40 mV
rms
60 mV
rms
Output V Load Regulation
-
1.7%
1.2%
1.7%
1.2%
BMM Max Battery Current (per
input)
100 A
-
-
-
-
BMM Max total Battery
Current through LVD
150 A
-
-
-
-
BMM LVD Threshold V
(Default)
-
21 V
42 V
21 V
42 V
BMM LVD Reconnect V
(Default setting)
-
25 V
50 V
25 V
50 V
BMM idle DC Power Draw
6
<1 W
-
-
-
-
5
Actual operating point may be lower due to battery charge requirement.
6
AC mains power off; backup battery connected; LVD open.
Table 32. Integrated DC-DC Converter Module Specifications
Parameters
12 V
24 V
Default Output Voltage (VDC)
13.8 VDC
27.6 VDC
Output Voltage Adjustment Range (VDC)
11.5
–15.5 VDC
23.0
–31.0 VDC
Input Voltage
20
–60 VDC
20
–60 VDC
Power Output
700 W
700 W
Default Current Limit (A)
50 A
25 A
Output Current Limit Adjustment Range (A)
10
–50 A
5
–25 A
V-output Line Regulation
+/− 0.2%
V-output Load Regulation
+/− 0.5%
Efficiency (peak)
92% (Typical)
Power Factor
0.99 (Typical)
0.99 (Typical)
Output ripple (rms)
20 mV
rms
30 mV
rms
Operating Temperature
−30°C to 50°C
Output Grounding
DC-DC Converter Module is floating, may be
connected with Positive or Negative ground
Safety
Designed to meet EN60950-1