Output State after Power Loss
: Sets the state for the output after the
LDM loses all input power, then recovers. The default setting is Restore
Last State. Select one of the following:
•
Restore Last State:
This will return the output relay to the
state prior to the reset event (default).
•
Enable Output:
This will turn the output on, regardless of its
previous state.
•
Disable Output:
This will turn the output off, regardless of its
previous state.
Ignore Circuit Breaker Status:
Select to disable alarms from this
output. Will prevent false alarms on an unused channel. The default
setting is Disabled.
Enable Power Cycling:
Select this box to enable output power cycling
for this output. Enabled outputs will automatically be re-enabled after
the "Power Cycle Delay Time" whenever the output is disabled using the
Output Off button on the "SETTINGS & CONTROL" tab, or when the
"Network Watchdog" is triggered. This feature is useful for remotely
resetting power to a router or other hardware required for the network
connectivity of the unit. The default setting is Disabled.
NOTE: The Power Cycle Delay time must be set with duration long enough
for the connected network hardware to fully reset for this function to
be effective. Multiple outputs that are disabled using Power Cycling
will be reenabled in sequence from output #1 to output #4.
Output Load-Shedding
Load shedding will disable specified outputs when the system DC voltage
reaches a preset threshold for at least 30 seconds. This will save battery
capacity for mission-critical load devices by turning off non-critical load
devices. Loads will be reconnected if "Load-Shedding Auto Recovery" is
enabled, and the DC voltage exceeds the "Recovery Threshold" for 60
seconds.
Enable Load-Shedding:
Select this box to enable load-shedding on this
output. The default setting is Disabled.
Load-Shedding Threshold:
Set the DC voltage (9.0–58.5 VDC) at
which the selected output will be disabled. The default setting is 42-volt
DC.
Recovery Threshold:
Set the DC voltage (10.5–60.0 VDC) at which the
selected output will automatically be reconnected. This value must be at