Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
34
of 84
3.4
Status Indicators and Alarms
The status of the Hybrid Ultra is indicated on the front display panel module
on units equipped with an ICM, or via the network GUI (see Section 4) on
remotely monitored units. It is also available through SNMP (see Section
4.8.2). Green "POWER" and red "FAULT" LEDs on the Power Modules,
along with the form-C alarm contacts on the rear panel indicate the core
status of unit.
There is an option on the Setup & Control tab in the GUI for most alarms to
send an e-mail to designated addresses for remote notification (see Section
4.8.3).
All alarms and warnings will be displayed on the front display screen on
Hybrid Ultra systems and entered in the Alarm History log (most recent 20
alarms listed) (see Section 3.2.6).
Most alarms reset automatically when the trigger condition is removed.
Major alarms such as a Module DC Output Failure or Module Configuration
Error require that the module be temporarily removed to cycle input power
and clear the fault.
Table 18. Power Module Alarms
(cont’d on next page)
Alarm
Condition
Trigger Condition
Module
Output
1
Red
LED
Green
LED
Alarm
Relay
Send
2
Power Failure
Loss of AC power
to module
Disabled
Off
Off
Active
Yes
Module
Operating
Normal operation
Enabled
Off
On
No
-
Configuration
Error
Different voltage
modules installed
Enabled
Off
On
No
Yes
Current Limit
(Warning only,
display will
flash)
Output current
approaches within
1 A of the max
current limit setting
Enabled
Off
On
No
-
Fan Failure
(700 W)
Fan is not
operating to spec
Enabled
Off
On
No
Yes
Low Fan RPM
(1,500 W)
Fan is not
operating to spec
Enabled
Off
On
No
Yes
Fan Failure
(1,500 W)
Fan stops
spinning
Disabled
On
Off
Yes
Yes
Manual
Disable
Output switched
off by ICM or GUI
Disabled
Blink
Off
No
-
Module
Removal
Module system
connections open
Disabled
On
Off
No
-