Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
19
of 84
3.2
Menu Structure
See the complete menu structure in the following diagram. Navigate through
the various screens using the four interface buttons.
Figure 13. ICM
Menu Structure (cont’d on next page)
NOTE: Connectors A , B and C show continuation of the structure from
one page to another.
MAIN SCREEN
SYSTEM STATUS
SYSTEM SETTINGS
INPUT VOLTAGE 120V
OUTPUT VOLTAGE 55.2V
OUTPUT VOLTAGE 55.2V
CURRENT LIMIT 28A
OUTPUT CURRENT 20.0A
DC OUTPUT ON
ADVANCED OPTIONS
BMM MODULE X
BMM MODULE X SETTINGS
BATT VOLTAGE 55.2V
DISCT VOLTAGE 42.0V
BATT CURRENT 0.0A
RECON VOLTAGE 48.0V
BATT SOC 100%
CHARGE CURRENT 18A
OVERCURRENT 50A
BATTERY TYPE LEAD ACID
BAT CAPACITY 100Ah
BAT RATE 10hr
LOW SOC ALARM 25%
TEMP-CO/cell -2mV/C
BMM EQUALIZE CHARGE
EQUALIZE CHARGE
VOLTAGE 60.0V
DISCHARGE TEST
DURATION 30min
STATUS READY
BMM DISCHARGE TEST
MAX TIME 60min
STOP VOLTAGE 44.0V
STATUS READY
DCDC CONVERTER MODULE X
DCDC MODULE X SETTINGS
INPUT VOLTAGE 55.2V
VOLTAGE 55.2V
OUTPUT VOLTAGE 13.8V
CURRENT LIMIT 50A
OUTPUT CURRENT 5.0A
OUTPUT ON
X
X
/X
/X
/X
X
X
X
ADJUST SETTINGS
ADJUST SETTINGS
ADJUST SETTINGS
X
X
A
/X
ADJUST SETTINGS
ADJUST SETTINGS
/X
X
B
C