Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
37
of 84
Alarm
Condition
Trigger Condition
Output
Relays
ICM
Required
Alarm
Relay
Send
2
Output
Overcurrent
Output current rises
above setting for 5 s
Closed
Yes
Active
3
Yes
Configuration
Error
LDM in wrong slot or
mixed polarity with BMM
No
change
Yes
Active
3
Yes
Load
Shedding
V drops below Load
Shed setting for 30 s
Open
Yes
Active
3
Yes
Output
Manually
Disabled
Output manually
disabled via ICM or GUI
page
Open
Yes
-
-
2
E-mail notifications only sent if enabled in the unit’s web-GUI E-mail Setup page, and either AC or DC
power is available for the system to be operational.
3
Contact active only if alarm enabled in the web-GUI module Setup page.
Table 22. Intelligent Control Module (ICM) Alarms
Alarm Condition
Trigger Condition
Alarm Relay
Send E-mail
2
Alarm Input
Contact open or close on
any Alarm input 1 to 4
Active (if set up on
Alarm Input page)
Yes
AC Input Failure
AC input falls below 90 VAC
Active
3
Yes
System
Overcurrent
Total output current on
system is >300 A for 20 s
Active
3
Yes
System Current
Limit
ALL Power Modules in
system at their current or
power limit for 15 s
Active
3
Yes
Communication
Bus Error
Internal communication bus
error condition
Active
3
-
2
E-mail notifications only sent if enabled in the unit’s web-GUI E-mail Setup page, and either AC or DC
power is available for the system to be operational.
3
Contact active only if alarm enabled in the web-GUI module Setup page.
4.0
OPERATION: GRAPHICAL USER INTERFACE
Connect to the intelligent Hybrid Ultra via Ethernet for full, secure access to
all system settings, status, and alarm conditions. Units with the Intelligent
Control Module (ICM) installed are equipped with a built-in web server that
can be accessed via any standard web browser on a network connected
computer or phone. No additional software is required on the unit.
4.1
Log In/Log Out
1.
Connect to the Hybrid Ultra by entering the IP address of the unit in
the location/address field of the browser as shown: