3.2.8
Notification Screens
Alarm Notification
When the unit triggers an alarm, the front display panel will be over-written
by the Alarms Active screen. Press Back
X
to return to the previous screen,
press Enter to jump to the Alarm History screen.
Alarms will be shown as they occur, press
Back
X
button to return to the previous
screen, press Enter for Alarm History
info.
Equalization Charge Notification
When an Equalization Charge is completed, the front display panel will be
overwritten with the Equalization Charge results screen. Press Enter or
Back
X
buttons to jump to the System Status screen.
Discharge Test Notification
When a Discharge Test is completed, the front display panel will be
overwritten with the Discharge Test results screen.
A notification will automatically appear
indicating the results of a Discharge Test at
the completion of the test. Press Enter or
Back
X
buttons to jump to the System
Status screen.
3.3
Password Reset
NOTE: Always record the LCD password when set, as it must be entered to
change any supply settings using the front display panel.
Do the following to clear the LCD password in cases where it is lost:
1.
Switch off the AC power to the unit.
2.
Simultaneously press the ENTER and BACK
X
buttons for more
than 15 seconds while restoring the AC power.
3.
Enter a new password (see Section 3.2.7) if password protection is
required.
Reset the GUI password back to the factory default (user: admin, no
password) by selecting "RESET COMM SETTINGS" in the Network Status
front display panel menu shown above (Section 3.2.7).