Module #x: Battery Management
Battery Voltage
: Shows voltage of battery #1. This number does not
specify polarity.
Battery Current
: Shows the current that is passing from, or to the
batteries. This number is negative if the battery is discharging; positive
if the battery is being charged; and shows 0A if the battery is fully
charged. This number represents both batteries if this is a dual BMM
(BMMD).
Battery Temperature
: Shows the temperature measured on the optional
ICT Battery Temperature Probe (ICT-TMP). If no probe is installed, the
unit will default to 25°C.
Net Ah Count
: Shows the Ah that has been consumed from the battery.
Will display 0 Ah if the batteries are fully charged. The batteries must be
fully charged for 24 hours before this field populates. Only displayed
when the unit is configured for lead-acid batteries.
Run-time Remaining
: Shows the estimated time in hours and minutes
before the battery is discharged. This is blank if the batteries are
charging. The batteries must be fully charged for 24 hours before this
field populates. Only displayed when the unit is configured for lead-acid
batteries.
Battery State of Charge
: Shows the estimated state of charge in %.
The batteries must be fully charged for 24 hours before this field
populates. Only displayed when the unit is configured for lead-acid
batteries.
Battery 2 Voltage
: Shows the voltage of battery #2. This field only
displays when a BMMD is installed.