Table 15. Default Reconnect Voltage Settings
Module
ICT700-24PM
ICT1500-24PM
ICT700-48PM
ICT1500-48PM
Threshold Voltage
25.0 VDC
50.0 VDC
Table 16. The Minimum Difference Between Disconnect and Reconnect Voltage
24 VDC Units
48 VDC Units
2 V
4 V
CHARGE CURRENT
: Set the "Battery Charge Current Limit" to limit the
maximum battery charge current provided, while still allowing the full
rated current to be drawn from the main output.
OVERCURRENT:
Set the "Battery Overcurrent" to receive an alarm
notification when the battery discharge or charge current exceeds the set
over-current level.
NOTE: Set the threshold to 0 A to disable this alarm (default setting).
BATT TYPE
: Configure the "Battery Type" of the battery used in the
system (Lead acid or Lithium Ion). If Lithium Ion type battery is selected,
the following battery parameters and settings will be unavailable. These
should be available from the integrated BMS.
•
Battery State of Charge
•
Run-time Remaining
•
Voltage Temperature Coefficient / cell
•
Equalize Charge
•
Battery Discharge Test
BATT CAPACITY:
Enter the combined battery capacity in Ah so the
system can estimate the total battery SOC%.
BATT RATE:
Set the battery rate (hrs.). This represents the discharge
rate specified by the battery manufacturer to determine the battery
capacity (usually will be 20 hr. or 10 hr. rate).
NOTE: Connecting batteries in parallel will increase the total Ah capacity,
while connecting batteries in series will increase the voltage with no
change to the Ah capacity.